The EPH Controls UFH5 is a 5 zone, 230Vac underfloor heating wiring centre that brings thermostats, thermal actuators, the manifold pump, the boiler call and the UFH valve together in one IP20 enclosure. It provides a volt-free heat enable output for a boiler or heat pump, a 230V pump output and a 230V UFH valve output, so a complete 230V wired underfloor heating system can be controlled from a single unit.
Each zone supports up to four actuators and has its own zone indicator LED, alongside power, heat enable and UFH valve LEDs. Zones 4 and 5 can be switched between underfloor heating and radiator or hot water duty, and three time inputs allow a 3-zone programmer to drive non-programmable thermostats. It mounts on a wall or DIN rail, carries a 5A fuse and works with EPH's range of 230V mains-operated thermostats.
3(1)A
Heat enable and pump contacts
2
Zones switchable UFH / RAD-HW
5 Years
Manufacturer warranty
How the zone 4 and 5 switches work
Set to UFH: a call for heat enables the actuator, boiler (heat enable), pump and UFH valve outputs. Set to RAD / HW: only the actuator is enabled. For the boiler to fire on a RAD / HW zone, wire the valve's auxiliary contacts (grey and orange) to the LS and LR terminals of the heat enable.
Compatibility notes
The UFH5 is a 230V wiring centre for mains-operated thermostats (for example RDTP, RDT, HDT, CDT2, CDTP2, CP4M and CDC2 cylinder thermostats) and 230V thermal actuators. It is not suitable for 24V actuators or thermostats. The maximum permissible load is 5A resistive.
Installation safety
Installation must be carried out by a qualified person in accordance with BS 7671. Isolate the supply before work. Best practice is to wire the manifold pump through a high-limit thermostat mounted on the manifold. If no UFH valve is fitted, the GR and OR terminals must be linked out; they are linked at the factory, so remove the link when a UFH valve is fitted.
Key Features
Five zones in one unit
Controls five thermostat zones with 230V actuator outputs, each with an indicator LED so faults are quick to trace.
Boiler and heat pump call
A volt-free heat enable relay switches the boiler or heat pump on a call for heat, rated 3(1)A.
Pump and UFH valve outputs
Dedicated 230V manifold pump output (3(1)A) and UFH valve output with grey and orange auxiliary terminals.
Zone 4 and 5 flexibility
Two zone switches let zones 4 and 5 serve underfloor, radiator or hot water circuits on the same wiring centre.
Programmer time inputs
Three time inputs let a 3-zone programmer control non-programmable thermostats: one input for zone 1, a choice of two for zones 2–4, a choice of three for zone 5.
Easy mounting
237 × 165 × 50 mm body that fixes to a wall through the base holes or clips onto DIN rail.
Technical Specification
General
Power supply
230Vac 50–60Hz
Switch output
SPDT 230Vac
Max. permissible load
5A resistive
Heat enable contact rating
3(1)A (volt free)
UFH pump contact rating
3(1)A
Max. actuators per zone
4
Indication
Power supply, heat enable, UFH valve and zones 1 to 5
Physical and Environmental
Dimensions
237 × 165 × 50 mm
Mounting
Wall mounted or DIN rail
Ambient temperature
0…45°C
Admissible humidity
5–95% RH
Factory default
Zone 4 and zone 5 switches set to UFH
Approvals and Warranty
Mains operated
Yes, with light indication
Frequently Asked Questions
How many actuators can each zone drive?
Up to 4 actuators per zone. Each zone has its own pair of L and N terminals for 230V thermal actuators, and the total load must stay within the 5A resistive limit.
Can I use zones for radiators or hot water?
Yes. Use the zone 4 and zone 5 switches to select RAD / HW instead of UFH. EPH shows a layout with three underfloor zones, one radiator zone and one hot water zone, each using a 2-port valve. To fire the boiler, wire the valve's auxiliary contacts to the heat enable LS and LR terminals.
Which thermostats work with the UFH5?
EPH's 230V mains-operated thermostats: programmable models such as RDTP, CDTP2 and CP4M, and non-programmable models such as RDT, HDT and CDT2, plus the CDC2 cylinder thermostat. Non-programmable thermostats take their time signal from a 3-zone programmer connected to the time inputs.
Is this a 24V wiring centre?
No. The UFH5 is a 230V unit. Systems using 24V thermostats and actuators need a 24V wiring centre.
How should the manifold pump be wired?
Connect the pump to the UFH pump terminals so it runs on a call for heat. Best practice is to route it through a high-limit thermostat mounted on the manifold. The pump output is rated 3(1)A.
What are the mounting options?
The enclosure measures 237 × 165 × 50 mm and can be screwed to a wall through the fixing holes in the base or mounted directly on DIN rail.