Compatibility and what is not included
This kit pairs with Samsung EHS Mono HT Quiet outdoor units (AE080BXYD, AE120BXYD and AE140BXYD series). Confirm your exact outdoor unit model before ordering. The kit does not include the hot water cylinder, 3-way valve, 2-way zone valves, mixing valve, additional pump, room thermostats or the optional Wi-Fi kit.
2 zone control
Two thermostat inputs and two 2-way valve outputs serve Zone 1 (underfloor heating) and Zone 2 (fan coil units or radiators). Heating and cooling signals are handled per zone.
Mixing valve control
Drives a 3-point mixing valve with the supplied 15 m TW4 sensor, so a high temperature zone and a low temperature zone can run side by side from one heat pump.
PV and SG Ready
Includes a 2 m PV or peak power control cable plus two SG Ready inputs that can force thermo off or step up the heating and DHW set temperature by one or two steps.
Hot water management
Controls a 3-way DHW diverting valve, reads a DHW tank sensor, accepts a solar pump or DHW thermostat signal and supports a booster heater up to 3 kW.
Backup heat options
Provides a 2 step backup heater control signal and a backup boiler output, so an electric heater or existing boiler can support the heat pump when required.
MWR-WW10N controller included
The wired touch controller connects on F3 and F4. Up to two controllers can be fitted on one kit as Main and Sub.
General
Type
Mono control kit, 2 zone
Packing size (W x H x D)
329 x 439 x 168 mm
Power supply
1 phase, 220-240 V, 50 Hz
Earth leakage breaker (ELCB)
Fitted, 30 A rated, 30 mA leakage
Supplied in the box
Wired remote controller
MWR-WW10N, 1 off
Temperature sensors (15 m)
DHW tank (yellow), mixing valve (blue), heater (black), 1 of each
Flow sensor
1 off, 1.5 m lead
PV or peak power control cable
Red, 2 m, 1 off
Tube connectors
OD 28.0 mm, left and right, with fasteners and O-rings
Sensor fitting items
2 sensor holders (OD 7.8 mm), 2 sensor clips, 4 cable ties, 2 aluminium tape, 2 rubber tape, 2 insulators
Backup heater connectors
Red, brown and white lead connectors
Documentation
Installation manual and user manual
Outputs (AC 230 V)
Water pump (B1/B6)
0.5 A, inverter pump up to 100 W, mandatory
Additional pump (B7/B8)
0.5 A, one pump up to 100 W, optional
Mixing valve (B2/B3/B5)
22 mA, CW and CCW drive
2-way valve Zone 1 and Zone 2
22 mA each, normally open or normally closed types
3-way valve for DHW (B15-B18)
22 mA, diverting type
Backup boiler signal (B4/B5)
10 mA control signal only
Backup heater control signal
Step 1 and step 2, AC 230 V, max 0.5 A, for a relay or contactor
Booster heater (TB-A1)
Direct connection, max 3 kW, output AC 230 V max 20 A
Inputs and sensors
Room thermostats (B21-B24)
AC 230 V input, heating and cooling signal per zone
Solar pump or DHW thermostat (B25/B26)
AC 230 V detection input, 10 mA
SG Ready (10P terminal block)
2 inputs, MIM-E03EN only
External zone sensors (10P terminal block)
Zone 1 flow, Zone 2 room, Zone 2 flow; 10 kOhm at 25 degrees C thermistor, B constant 3435 K, MIM-E03EN only
Flow sensor set point
7 L/min for AE080BXYD, AE120BXYD and AE140BXYD
Cabling
Supply cable, no booster heater
1.5 mm2 x 3 up to 10 m, 2.5 mm2 x 3 over 10 m
Supply cable, with booster heater
4.0 mm2 x 3 up to 10 m, 6.0 mm2 x 3 over 10 m
Controller connection
F3 and F4 on TB-C, max 100 m, AWG20 recommended
Controller wall plate
120 x 120 x 19 mm
Outdoor unit communication
2 core cable, F1 and F2 on TB-C